Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM02918
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/14/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/30/2006 | ELECTRIC - INTERMEDIATE | Denied | 1. ROMEX OR TYPE NM NOT ALLOWED PER 334.12 & 518.4 NEC SEE PLANS, PLANS CALL FOR CONDUIT OR MC 2. #12 AWG CU. MIN. SIZE CONDUCTOR PER PLAN, #14 INSTALLED. SEE PLANS. 3. CHECK SWITCH BOX FILL FOR CONDUCTORS. |