Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/29/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 12/20/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO WATER TEST DWV SYSTEM 2. NAIL PROTECT AB'S TOP & BOTTOM PLATES 3. SECURE 90 VENT THROUGH ROOF 4. NAIL PROTECT ELECTRIC THROUGHOUT 1 1/4" CLEARANCE NEEDED. 5. REMOVE ALL UNUSED ELECTRICAL 6. TERMINATE SMOKE DETECTOR IN APPROVED BOX/LIVING ROOM FIXTURE NOT ON PLAN. 7. ALL LUMBER TOUCHING FLOOR MUST BE TREATED 8. OUTLETS MISSING BEDROOM 1 9. ELIMINATE ALL UNUSED WIRE IN WALLS 10. MISSING OUTLET KITCHEN SOUTH WALL 11. OUTLET NEEDED 3' FROM REAR DOOR 12. SMOKE DETECTOR MISSING PER PLAN LIVING ROOM 13. OUTLETS MISSING LIVING ROOM 14. SECURE ALL ROMEX 8" FROM BOXES 15. BASEBOARD HEATER REQUIRES DEDICATED 20 AMP CIRCUIT. 16. EXHAUST FAN MISSING PER PLAN 17. MAIN SERVICE PANEL NOT LOCATED PER PLAN IS MECHANICAL NOT ON PLAN WINDOW UNIT. |
|
| 11/21/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) IT APPEARS THAT INTERIOR FINISH FLOOR IS SAME ELEVATION AS EARTH 2) OSB MUST BE ELVEVATED 6" MINIMUM FROM EARTH 3) 10 POUND MINIMUM TEST REQUIRED ON GAS LINE 4) STABILIZE SHOWER/WALL MISSING 5) STUCC SHALL HAVE WEEP SCREED AND RAISED 4" FROM EARTH |
|
| 11/17/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/09/2006 | FRAMING | Cancelled | IVRS - RI canceled |