Permit: T06CM02908

Parcel: 122030290

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
01/31/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
YOU HAVE TO DO A BETTER JOB SEALING ABANDONED DUCT & REGISTERS. DO NOT USE PUTTY OR SHEETROCK SCREWS ON SHEETMETAL. PROVIDE SCREWS ON ALL 4 SIDES. DO THIS PRIOR TO SHEETROCK. FURNACE VENT NOT TO CODE.
HOW ARE YOU GOING TO HEAT UPSTAIRS?