Permit: T06CM02908

Parcel: 122030290

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/04/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
05/25/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CORRECT THE FOLLOWING ITEMS:
1. SECURE DW HOSE
2. PROVIDE CLEANOUTS AT KIT. SINKS AND LAUNDRY
3. SEAL ROOF PENETRATIONS W/FLASHINGS
4. HAMMER ARRESTORS REQUIRED AT LAUNDRY
5. COVER OR INSTALL CAST IRON AT EXPOSED ABS FITTINGS AT LAUNDRY.
6. DRAINAGE FITTINGS REQUIRED ON VENTS BELOW FLOOD LEVEL OF KIT. SINK
7. CAULK WCS AT CONTACT TO FLOOR
8. SADDLE TAPS ARE NOT CODE APPROVED FITTINGS.
INSTALL UPC APPROVED VALVES.
9. HB VAC BREAKERS
10. SUPPORT ON B VENTS
11. COMBUSTION AIR AT FURNACE
12. WATER HEATER INSTALLED ON WOOD PLATFORM REQUIRES DRAIN PAN.
05/22/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
HB MISSING VAC BREAKER
INSP STOPPED
COMPLETE WORK THEN CALL FOR INSP.
05/15/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE NEW GAUGE
2. LIST NOT COMPLETE