Permit: T06CM02908

Parcel: 122030290

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Date Description Inspector Results Comments
05/25/2007 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection :*
05/22/2007 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1.5 PSI TEST DOES NOT MEET UPC TESTING REQUIREMENTS
USE LISTED B VENT SUPPORT AT WH VENT.
05/15/2007 PLUMBING - GAS PRESS TEST FNL Not ready for Inspection IVRS - Inspection :*
01/31/2007 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. UNIT #1 DOWNSTAIRS INTERMEDIATE INSIDE OK TO COVER
2. PROVIDE A CITY APPROVED GAS ISOMETRIC DRAWING THAT SHOWS WHICH GAS APPLIANCES ARE FOR WHICH UNIT NUMBER.
3. REMOVE BENT/STRAINED PIPING. SUPPORT & SECURE ALL GAS PIPING.
4. REMOVE TEE BELOW PIPING AT METER LOCATION.
5. COMPLETE PIPING TO STOVE IN UNIT #2
6. PROVIDE CLEARANCE BETWEEN GAS WH AND GAS METER FURNACE WILL REQUIRE INSPECTION.
7. FURNACE HAS VENTING & COMBUSTION.
01/26/2007 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/18/2007 PLUMBING - GAS PRESS TEST FNL Not ready for Inspection IVRS - Inspection :*