Permit: T06CM02908

Parcel: 122030290

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
02/20/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
02/13/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE A PRESSURE TEST ON GAS PIPING.
2. PROVIDE SWEEPS AT 90 DEG. CHANGES OF DIRECTION ON LAV WASTE.
3. PROVIDE WATER TEST THRU ROOF ON WASTE & VENT.
4. PROVIDE TEST ON TUB OVERFLOW GASKET BY INSTALLING PLUG AND FILLING SECOND STORY TUB TO OVER FLOW LEVEL.
5. CAP OLD KIT DRAIN PIPING W/PIPE CAP OR PLUG.
6. TYPE M COPPER NOT APPROVED FOR OUTDOORS.
02/01/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) UNIT #2 TEST ON TUB DRAIN PIPING IS OK
2) TEST TUB WASTE AND OVERFLOW GASKETS BY FILLING TUB TO FLOOD LEVEL
3) SUPPORT PIPING WITH APPROVED PIPE SUPPORTS NOT P TAPE
4) REMOVE EXCESS FLUX FROM SOLDIER JOINTS
5) USE APPROVED DRAINAGE FITTINGS ON LAV-I WILL ACCEPT EXISTING PIPING IF IT WILL HOLD A WATER TEST THRU ROOF
01/31/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*