Permit: T06CM02908

Parcel: 122030290

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
06/04/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
01/26/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
ROUGH PLUMBING OK UNIT ONE
ABS CANNOT BE EXPOSED
EXPOSED COPPER MUST BE INSULATED
CALL FOR INTERMEDIATE INSPECTION WHEN READY
USE SWEEPS ON TRAP ARMS
CAP ABANDON SINK DRAIN
SECURE AND ISOLATE PEX
GAS PIPING UNDER STRAIN. NOT PROPERLY SUPPORTED
NOT COMPLETE
GAS PIPING LEAKING, SEPARATE GAS FOR EACH UNIT.
01/18/2007 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
L & G PROF. PLUMBING
1. NEW LAVITORY WASTE PIPE CONNECTION TO BELOW SLAB GALVANIZED NOT ACCEPTABLE (701.1)
2. CONNECT NEW LAV PIPING TO NEW KIT. SINK DRAIN LOCATED WITHIN TWO FEET.
3. PROTECT PIPING PENETRATING CONCRETE.
4. INSTALL TEST FITTING IN DIRECTION OF FLOW.
5. LAUNDRY WASTE IS NOT VENTED OR UNDER TEST.
6. PLASTIC PIPING CANNOT BE EXPOSED.
7. GAS PIPING SHALL BE PROPERLY INSTALLED; SUPPORTS, FITTINGS, PROTECTION OF BELOW GRADE PIPING.
8. INSTALL HB VACUUM BREAKERS ON HOSE BIBBS.
9. EXPOSE YARD PIPING OR PROVIDE PROOF OF INSPECTION.
10. SECURE AND ISOLATE WATER PIPING.
11. INSTALL ANTI-SCALD SHOWER DIVERTER
12. 1/2" EXPOSED PIPING NOT ACCEPTABLE (313.6)