Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2007 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
| 04/19/2007 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PANEL TO NOT SIT BACK MORE THAN 1/4" FROM SURFACE 2. CLEAN EXCESS TRASH FROM BOTTOM OF PANEL 3. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR 4. FILL UNUSED OPENINGS IN BOTTOM OF PANEL 5. CANNOT SLEEVE CONDUCTORS FROM CONDUIT TO PANEL IF NOT AN APPROVED CABLE OR CONDUIT. 6. CANNOT DOUBLE NEUTRALS. |
|
| 03/22/2007 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE A BUSHING TO PROTECT CABLES IN BACK OF SERVICE AND FILL UNUSED PORTION WITH A NON-COMBUSTIBLE PRODUCT. 2. INSTALL BREAKERS & DEVICES |