Permit: T06CM02908

Parcel: 122030290

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
04/26/2007 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
04/19/2007 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PANEL TO NOT SIT BACK MORE THAN 1/4" FROM SURFACE
2. CLEAN EXCESS TRASH FROM BOTTOM OF PANEL
3. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR
4. FILL UNUSED OPENINGS IN BOTTOM OF PANEL
5. CANNOT SLEEVE CONDUCTORS FROM CONDUIT TO PANEL IF NOT AN APPROVED CABLE OR CONDUIT.
6. CANNOT DOUBLE NEUTRALS.
03/22/2007 ELECTRIC - TEMPORARY SERVICE Not ready for Inspection IVRS - Inspection :*
1. PROVIDE A BUSHING TO PROTECT CABLES IN BACK OF SERVICE AND FILL UNUSED PORTION WITH A NON-COMBUSTIBLE PRODUCT.
2. INSTALL BREAKERS & DEVICES