Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM02902
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/28/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/21/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. WATER HEATER NOT LISTED FOR OUTDOORS - CHECK 2. WIRING METHOD TO WATER HEATER NOT RAINTITE 3. HAVE TO HIGH OVERCURRENT PROTECTION FOR A.C AND REMOVE OUTER BRACES. 4. INSTALL ANTI-TIP DEVICE ON RANGE. 5. INSTALL ALL COVER SCREWS. 6. SMOKE DETECTORS ALL NEED TO BE INTER-CONNECTED. 7. BEDROOM LIGHTS, SMOKES AND RECEPTACLES REQUIRE ARC FAULT PROTECTION. AT FURNACE: 8A. NEED PROPER CONNECTOR FOR ROMEX B. DISCONNECT NOT ACCESSIBLE C. STRAP FLEX D. OVERCURRENT PROTECTION TO HIGH E. MARK FURNACE IF HEAT KIT INSTALLED CHECK FOR THESE AND OTHER PROBLEMS IN ALL UNITS BEFORE FINAL. |