Permit: T06CM02902

Parcel: 115150290


Addresses:

2115 N ORACLE RD 01


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM02902

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/28/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/21/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. WATER HEATER NOT LISTED FOR OUTDOORS - CHECK
2. WIRING METHOD TO WATER HEATER NOT RAINTITE
3. HAVE TO HIGH OVERCURRENT PROTECTION FOR A.C AND REMOVE OUTER BRACES.
4. INSTALL ANTI-TIP DEVICE ON RANGE.
5. INSTALL ALL COVER SCREWS.
6. SMOKE DETECTORS ALL NEED TO BE INTER-CONNECTED.
7. BEDROOM LIGHTS, SMOKES AND RECEPTACLES REQUIRE ARC FAULT PROTECTION.

AT FURNACE:
8A. NEED PROPER CONNECTOR FOR ROMEX
B. DISCONNECT NOT ACCESSIBLE
C. STRAP FLEX
D. OVERCURRENT PROTECTION TO HIGH
E. MARK FURNACE IF HEAT KIT INSTALLED

CHECK FOR THESE AND OTHER PROBLEMS IN ALL UNITS BEFORE FINAL.