Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM02896
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/18/2006 | FRAMING | Approved | IVRS - Inspection :* | |
10/09/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) OK TO SHEETROCK 2) AT NEXT INSPECTION NEED PAPERWORK FOR REAR BATHROOM RETRO |
|
09/27/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL GLUED PERM CAP ON 2" UNUSED PIPE 2) LAUNDRY DRAIN OPT SINK NOT PLUMBED PER CODE 3) WET VENTING ALLOWED FOR TRAP ARMS ONLY 4) REPAIR REAR SHEAR 5) TUB BACKING AT SIDE 6) INTERIOR SHEARWALLS #3, 4 #3 HLTT PINS AT 6" ON CENTER-#4 1/2 DIAMETER A.B.'S AT 48" ON CENTER 7) NAIL STUD AT KITCHEN OVEN VENT 8) SECURE ALL MECH DUCTS, BLK 3 SIDES 9) GAS, DWV AND H20 OK 10) EXT. CLIP NOT SIGNED OFF |
|
08/10/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NO INSPECTION CARD ON SITE |
|
08/09/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STILL MISSING 2 X 6 KING STUD AT PATIO HEADER 2) HOLDOWNS STILL NOT IN |
|
08/07/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) HOLDOWNS MISSING 2) HEADER WRONG SIZE 3) ADD KING STUD |