Permit: T06CM02887

Parcel: 113101320


Addresses:

1709 E SILVER ST


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T06CM02887

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/25/2007 BUILDING - FINAL Approved IVRS - Inspection :*
06/01/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OUTLET MISSING AT COUNTER TOP
2) OUTLET SHALL BE 4'-0" ON CENTER AND NOT OVER 24" FROM EDGES
3) REMOVE OUTLET FROM UNDER COUNTER TOP WITH OVER 6" OF OVERHANG
4) PAINT ROOF ABS VENTS
5) TRAP REQUIRED AT CONDENSATION LINE
6) FASCIA MISSING AT REAR PORCH
7) ANTI-TIP MISSING AT RANGE
8) BUBBLE COVER REQUIRED AT EXT. OUTLETS
9) ARC FAULT BREAKERS REQUIRED AT BEDROOMS