Permit: T06CM02886

Parcel: 116273870

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
02/05/2008 BUILDING - FINAL Approved IVRS - Inspection :*
02/01/2008 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SERVICE PANEL "A" ALUMINUM FEEDER WIRE NEED NO-LOX
2) CLEANOUT NOT COMPLETE OR EAST WALL
3) GRADING FOR DRAINAGE NOT COMPLETE
4) MISSING ANTI-SIPHON ON HOSE BIB
5) SEAL BASE OF TOILETS
6) FIREPLACES NEED APPROVED GAS VALVES
01/30/2008 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER CONTRACTOR