Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM02885
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/04/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL |
|
11/30/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH PREVIOUS ITEMS #2, 3, 4, 9 |
|
11/28/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SUPPORT VDV CABELING AS PER 725.3 & 6, 800.3 & 6 2. SUPPORT M/C CABLE WITHIN 12" OF BOX & 6' 3. SUPPORT CONDUITS AS PER CODES. 4. USE APPROVED SUPPORT FOR M/C CABLE 5. KITCHEN RECEPTACLES TO BE GFCI 210.8 6. SUPPORT FIXTURES 7. TIGHTEN LOOSE CORD CONNECTOR 8. EM LIGHTING TO BE ON AREA SERVED 700.12 9. BOXES MORE THAN 1/4" FROM BOX T0 SERVICE NEED AN APPROVED EXTENDER RING 314.20 |
|
09/18/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
09/15/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SEPARATE GROUNDS AND NEUTRALS AT SUB-PANEL 2. IDENTIFY GROUNDED/NEUTRAL CONDUCTOR AT SUBPANEL & METER CABINET. 3. CLEAN SURFACE UNDER LUG FOR GROUNDING 250.12 4. PLEASE PROVIDE REJECTION PINS. |