Permit: T06CM02884

Parcel: 12701003W


Addresses:

4911 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM02884

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/13/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
OK TO COVER WALLS
11/09/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
11/08/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO COVER WALLS BEHIND WC AND LAVS ONLY. DO NOT BURY THREADED FITTINGS-TEST TEES. MISSION COUPLINGS AT URINALS ARE NOT SIZED FOR USE ON COPPER, ALSO NOT INTENDED TO BE USED OVER THREADED ADAPTOR, PIPING WILL NOT FACILITATE INSTALLATION OF URINAL (PIPING OUT TO FAR FROM WALL). PIPING MAY INTERFERE WITH MOUNTING BRACKET AT URINAL. HAMMER ? REQUIRED ON QUICK CLOSING VALVES.
SAFETY PLATES REQUIRED WHERE PIPING IS LESS THAN 1 1/4" FROM STUD
REMOVE EXCESS FLUX FROM JOINTS
CLOSET FLANGES SHALL BE SECURED TO FF ( THIS CAN BE INSPECTED AFTER FLOORING)
TEST TEES SHALL BE TRIMMED OUT AS CLEANOUTS FOR ACCESSIBILITY
11/07/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE CORRECT DRAINAGE FITTINGS & COMPLETE URINAL.
2. SECURE ALL PIPING CORRECTLY.
3. SUPPORT ALL OVERHEAD PIPING CORRECTLY.
4. NO FEMALE ABS THREADED FITTING IN UNACCESSIBLE LOCATION.
5. CLOSET FLANGE SHALL BE 1/4" ABOVE FINISH SURFACE AND BE SECURE.

MAY NOT BE A COMPLETE LIST.