Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM02884
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/13/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* OK TO COVER WALLS |
|
11/09/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
11/08/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO COVER WALLS BEHIND WC AND LAVS ONLY. DO NOT BURY THREADED FITTINGS-TEST TEES. MISSION COUPLINGS AT URINALS ARE NOT SIZED FOR USE ON COPPER, ALSO NOT INTENDED TO BE USED OVER THREADED ADAPTOR, PIPING WILL NOT FACILITATE INSTALLATION OF URINAL (PIPING OUT TO FAR FROM WALL). PIPING MAY INTERFERE WITH MOUNTING BRACKET AT URINAL. HAMMER ? REQUIRED ON QUICK CLOSING VALVES. SAFETY PLATES REQUIRED WHERE PIPING IS LESS THAN 1 1/4" FROM STUD REMOVE EXCESS FLUX FROM JOINTS CLOSET FLANGES SHALL BE SECURED TO FF ( THIS CAN BE INSPECTED AFTER FLOORING) TEST TEES SHALL BE TRIMMED OUT AS CLEANOUTS FOR ACCESSIBILITY |
|
11/07/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE CORRECT DRAINAGE FITTINGS & COMPLETE URINAL. 2. SECURE ALL PIPING CORRECTLY. 3. SUPPORT ALL OVERHEAD PIPING CORRECTLY. 4. NO FEMALE ABS THREADED FITTING IN UNACCESSIBLE LOCATION. 5. CLOSET FLANGE SHALL BE 1/4" ABOVE FINISH SURFACE AND BE SECURE. MAY NOT BE A COMPLETE LIST. |