Permit: T06CM02874

Parcel: 133143320

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/10/2014 ELECTRIC - FINAL Approved PER BU FINAL
11/28/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH PREVIOUS ITEMS #2 & #4
09/21/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. CLEAN EXCESS PAINT OFF OF DEVICE TERMINAL SCREWS.
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RINGS.
3. BOXES ALLOWED UP TO 1/8" OPEN AROUND BOX 314.21
4. CORRECTLY IDENTIFY 3 WAY CONDUCTORS IN FIXTURE ALSO PROTECT CABLE ENTERING FIXTURE AND USE AN EXTENDER RING.
6. SUPPORT PVC CONDUIT AT SIDE OF PANEL
7. FITTING TO PROPERLY SEAT IN CORRECT SIZED HOLE OF PANEL AND A LOCK NUT IS NEEDED.
8. USE BREAKERS LISTED FOR USE BY MANUFACTURER.
9. ONLY ONE CONDUCTOR TO A BREAKER TERMINATION LUG.