Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/10/2014 | ELECTRIC - FINAL | Approved | PER BU FINAL | |
| 11/28/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH PREVIOUS ITEMS #2 & #4 |
|
| 09/21/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CLEAN EXCESS PAINT OFF OF DEVICE TERMINAL SCREWS. 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RINGS. 3. BOXES ALLOWED UP TO 1/8" OPEN AROUND BOX 314.21 4. CORRECTLY IDENTIFY 3 WAY CONDUCTORS IN FIXTURE ALSO PROTECT CABLE ENTERING FIXTURE AND USE AN EXTENDER RING. 6. SUPPORT PVC CONDUIT AT SIDE OF PANEL 7. FITTING TO PROPERLY SEAT IN CORRECT SIZED HOLE OF PANEL AND A LOCK NUT IS NEEDED. 8. USE BREAKERS LISTED FOR USE BY MANUFACTURER. 9. ONLY ONE CONDUCTOR TO A BREAKER TERMINATION LUG. |