Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2006 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 08/31/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - PROVIDE CONDENSATE DRAIN AS PER PLANS. - PROVIDE FHA STRAPS AT DRYER VENT. - BLOCKS & CLAMPS MISSING FROM EXISTING CONDENSATE DRAINS ON ROOF. |
|
| 08/30/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - PROVIDE CONDENSATE DRAIN LINE AS PER PLANS. - IF EXISTING DRAINS ARE NOT TERMINATED TO AN APPROVED LOCATION THEY WILL HAVE TO BE CHANGED. - PROVIDE PLATE STRAPS AT DRYER VENT. - ON FINAL PROVIDE A COPY OF THE CERTIFIED AIR BALANCE REPORT. |