Permit: T06CM02867

Parcel: 127010090


Addresses:

5110 E 5TH ST #100

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/13/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/01/2006 ELECTRIC - FINAL Cancelled IVRS - RI canceled
11/01/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PLEASE VERIFY LISTING AND LABELING OF EQUIPMENT
-- 110.3
2. PROTECT CONDUCTORS FROM SHARP METAL EDGES AT LIGHT FIXTURES.
3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING -- 314.20
4. FIXTURE SCHEDULE -- PLEASE REVISE TO REFLECT WORK DONE AND NEW ENERGY LOADS.
5. CHECK ROOF NEXT TIME.