Permit: T06CM02820

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM02820

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/13/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/03/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
DAN 661-816-5959
PAID CK #1271 $108.00
AFTER HOURS INSPECTION

1. MISSING EMERGENCY CAN WEST RETAIL AREA
2. CHECK BOX FILL, J-BOX GROUNDING - BACK AREAS
3. CHECK PANEL DIRECTORYS

ROOFTOP -
IDENTIFY RTU-1 & RTU-2 DISCONNECTS
NEED GFI SERVICE RECEPTACLE
NO SELF TAP SCREW TO GROUNDS
GROUND GUTTER UNDER DISCONNECT

OK TO OCCUPY
09/08/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
OK TO COVER ELECTRICAL IN WALLS
NOTE: ADD ELECTRICAL ABOVE CEILING
AND ELECTRICAL INTERMEDIATE TO YOUR PERMIT PRIOR TO NEXT INSPECTION.
09/06/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
STRAP EMT WITHIN 3' AND NO MORE THAN 10'
STRAP MC WITHIN 12"
FINISH WALL WIRING
BRACE BOXES AS NEEDED
5/8 MUD RINGS
WORK IN PROGRESS