Permit: T06CM02820

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
11/13/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
11/01/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING COVER FRONT RETAIL AREA
10/31/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SECURE ALL FIXTURES TO GRID - NEC 300
2. SUPPORT WIRES FOR ALL FIXTURES -- NEC 300
3. ALL SUPPORT WIRES CONNECTED @ BOTH ENDS -- NEC 300
10/30/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
10/28/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. SUPPORT FOR ELECTRICAL TO BE AS PER 300.11 -- INDEPENDENTLY SUPPORTED AND AT BOTH ENDS.
2. VDV CABELING TO BE SUPPORTED PER 725.6, 760.6, 300.11
3. SUPPORT WIRES NEEDED FOR TRACK LIGHTING
4. FILL UNUSED OPENINGS - NOT FITTINGS.
5. SUPPORT M/C CABLE WITHIN 12' OF BOXES
6. SUPPORT CONDUITS 3' & 10'

OK TO TILE EXCEPT AS NOTED

RECEIVED MONEY ORDER #0602734994 FOR $108.00 --
AFTER HOURS INSP.
10/25/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*