Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM02820
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/13/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/25/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ELECTRICAL COVER IN BATHROOMS. |
|
10/20/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CEILING COVER CIRCLE CEILING HALLWAY & DRESSING ROOM HARD LID AFTER YOU REMOVE UNUSED RACEWAYS AND INSTALL K.O BLANKS AS NEEDED. |
|
10/19/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FINISH WIRE PULLING ABOVE HARD LID. 2. STRAP MC WITHIN 12" OF TERMINATION. 3. STRAP EMT WITHIN 3' (SEE EXCEPTION) OF BOX 4. REMOVE OR TAG UNUSED LOW VOLTAGE WIRING 5. SUPPORT WIRES CONNECTED @ BOTH ENDS. 6. FIRE ALARM WIRE PROPERLY SUPPORTED & IDENTIFY BOXES WITH TERMINATIONS (RED) 7. CHECK BOX FILL AND ADD EXTENSION AS REQUIRED. 8. REMOVE UNUSED RACEWAYS & CONDUCTORS AS REQUIRED. 9. MAKE SURE EMERGENCY LIGHTING MEETS NEC 700.12 (2002) |
|
09/26/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* FRONT AREA HARD LID *NOTE: STRAP MC AS REQUIRED. |