Permit: T06CM02820

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM02820

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/13/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/25/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRICAL COVER IN BATHROOMS.
10/20/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CEILING COVER CIRCLE CEILING HALLWAY & DRESSING ROOM
HARD LID AFTER YOU REMOVE UNUSED RACEWAYS AND INSTALL K.O BLANKS AS NEEDED.
10/19/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FINISH WIRE PULLING ABOVE HARD LID.
2. STRAP MC WITHIN 12" OF TERMINATION.
3. STRAP EMT WITHIN 3' (SEE EXCEPTION) OF BOX
4. REMOVE OR TAG UNUSED LOW VOLTAGE WIRING
5. SUPPORT WIRES CONNECTED @ BOTH ENDS.
6. FIRE ALARM WIRE PROPERLY SUPPORTED & IDENTIFY BOXES WITH TERMINATIONS (RED)
7. CHECK BOX FILL AND ADD EXTENSION AS REQUIRED.
8. REMOVE UNUSED RACEWAYS & CONDUCTORS AS REQUIRED.
9. MAKE SURE EMERGENCY LIGHTING MEETS NEC 700.12 (2002)
09/26/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
FRONT AREA HARD LID
*NOTE: STRAP MC AS REQUIRED.