Permit: T06CM02807

Parcel: 126042180


Addresses:

822 N COLUMBUS BL

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
07/25/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
TEST OK
UTILITY CLEARANCE GIVEN
07/12/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
SYSTEM NOT HOLDING PRESSURE
06/23/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
200 PSI GAUGE NOT ACCEPTABLE
PROVIDE TEST WITH 1/10 PSI INCREMENTATION GAUGE
INSTALL WH VENT - USE TYPE B VENT
VENT SHALL TERMINATE 1' ABOVE SIDE WALL.
INDOOR APPLIANCES LOCATED OUTSIDE ARE REQUIRED TO BE PROTECTED BY AN ENCLOSURE.
PROVIDE ELECTRICAL BONDING OF GAS LINE.
HAVE AGA VALVES & FLEXES ON SIGHT.
INSTALL SEDIMENT TRAP AT WH.
05/31/2006 PLUMBING - GAS PRESSURE TEST Cancelled NOT READY FOR GAS INSPECTION