Permit: T06CM02804

Parcel: 140551030

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
08/15/2006 FRAMING Approved IVRS - Inspection :*
08/09/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BENT/RESTRICTED SUPPLY DUCT BOOT BY FAU
2) LEAK ON 3" STACK AT GARAGE
3) CONNECT LAUNDRY EXHAUST FAN DUCT
4) HOLDOWN BOLTS MISSING
5) SHIM 4 X 6 POST TO GLB HEADER KITCHEN
6) PEX MUST BE 12" FROM CAN LIGHTS
7) PROVIDE SHEAR TRANSFER BEHIND DUCT BEDROOM 2 AND COMPLY WITH 5/DT1
8) SEAL LATHE PENETRATIONS
9) HORIZONTAL VENTING BELOW 6" FIXTURE FLOOD ABOVE RIM NOT ALLOWED AT MASTER BATH
10) STAIR STRINGERS MISSING ITT HANGERS PER 10/DT2
11) SEAL FLOOR PENETRATION AT TUBS