Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T06CM02790
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/27/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) OK FOR FINAL |
|
06/05/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 3 PHASE ELECT. SWITCH, BASE AND FLEX BLOCKING CLEAR ACCESS TO ELECTRIC/COMPRESSOR COMPARTMENT ON UNIT. THESE NEED TO BE RELOCATED. 2. THESE ARE COMB. ROOFTOP UNITS. WHERE ARE GAS PIPING CONNECTIONS? 3. ROOF ACCESS. SEE SEC. 306.5 REAR PARAPET WALL IS IN EXCESS OF 30"; TOP DOWN TO ROOF. PROVIDE PERMANENT MEANS OF ACCESS. |
|
06/01/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* NEED ROOF ACCESS TO CHECK NEW ROOFTOP A/C EQUIP. |
|
05/25/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. INSULATE EXPOSED PC. OF SUPPLY GALV. TEE IN REAR STOCK RM. 2. NEED VISIBLE, AUDIBLE SIGNED PANEL ON GRID NEAR SMOKE ALARM. SEC. 606.4.1, IMC 2003 3. LEAVE APPROVED PLAN ON JOB. |