Permit: T06CM02788

Parcel: 11623102Y


Addresses:

942 W 21ST ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
05/29/2008 FRAMING Approved IVRS - Inspection :*
05/28/2008 FRAMING Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER OWNER
05/27/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NOT ENOUGH PRESSURE FOR GAS TEST
2) WATER STACK NOT6 FILLED COMPLETELY
3) NEED FIRE SEAL MECHANICAL DUCT CHASE
4) NEED TO BLOCK COMBUSTION AIR VENTS
5) PROTECT DRYER VENT THRU CEILING
6) NEED TO PROTECT WATER LINES 2ND FLOOR BATH
7) NEED TO PUT CONDUCTOR WIRE IN ELECTRIC BUSS AT MASTER CLOSET
8) NEED TO FIRE SEAL ALL CHASES
9) NEED ROCK WOOL AT BATH TUB FLOOR
10) NEED TO COMPLETE FIREPLACE FLUE AND NEED INSTALLATION INSTRUCTIONS
04/29/2008 FRAMING Not ready for Inspection IVRS - Inspection :*
WITH INTERMEDIATES