Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/29/2008 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/28/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER OWNER |
|
| 05/27/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NOT ENOUGH PRESSURE FOR GAS TEST 2) WATER STACK NOT6 FILLED COMPLETELY 3) NEED FIRE SEAL MECHANICAL DUCT CHASE 4) NEED TO BLOCK COMBUSTION AIR VENTS 5) PROTECT DRYER VENT THRU CEILING 6) NEED TO PROTECT WATER LINES 2ND FLOOR BATH 7) NEED TO PUT CONDUCTOR WIRE IN ELECTRIC BUSS AT MASTER CLOSET 8) NEED TO FIRE SEAL ALL CHASES 9) NEED ROCK WOOL AT BATH TUB FLOOR 10) NEED TO COMPLETE FIREPLACE FLUE AND NEED INSTALLATION INSTRUCTIONS |
|
| 04/29/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* WITH INTERMEDIATES |