Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T06CM02781
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2006 | BUILDING - FINAL | Approved | ||
| 07/24/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ARC FAULTS WON'T TRIP 2) DEAD OUTLET OFFICE 3) LABEL HEAT STRIP 4) LABEL NEUTRAL IN SERVICE 5) PLUG HOLE AT SERVICE PANEL 6) MAX 35 AMP FUSE AT A/C 7) LABEL NOT H20 BOND 8) NEED 3 CERTS |