Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM02780
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* NEED 2X6 AT 10' 0" O.C FLR TRUSSES STRONG BACKS |
|
| 06/12/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CORRECT REVERSE SLOPE 3" IN CENTER WALL 2) CODE SECTION 908.1 UPC CANNOT WET VENT ANYTHING BUT TRAP ARMS 3) OK TO SHEETROCK OTHER AREAS |
|
| 06/07/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 2ND FLOOR PLUMBING NOT PLUMBED PER PLAN OR CODE 2) NEED CLARIFICATION ON EXT. 1ST AND 2ND FLOOR ATTACHMENT, STRAPS AND BELLY BANDS 3) NAIL BOTTOM PLATE TO FLOOR 6" ON CENTER CAN ONLY, FIND DETAIL REFERING TO SHEARWALL, NOT REGULAR WALLS 4) FHA STRAP AT DRYER DUCT 5) TWO DAMAGED FLOOR TRUSSES, NEED REPAIR 6) OK TO INSULATE EXT. WALLS 7) REAR BATH TRAP ARMS TO LONG UNVENTED FIXTURES 8) 2" TRAP ARM OVER 5'-0", MUST GO 6" ABOVE FLOOD RIM BEFORE GOING HORIZONTAL 9) ITEM 03050 NOT REQUIRED/ALL ELECTRIC |