Permit: T06CM02780

Parcel: 141316190

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM02780

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/14/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
NEED 2X6 AT 10' 0" O.C
FLR TRUSSES
STRONG BACKS
06/12/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CORRECT REVERSE SLOPE 3" IN CENTER WALL
2) CODE SECTION 908.1 UPC CANNOT WET VENT ANYTHING BUT TRAP ARMS
3) OK TO SHEETROCK OTHER AREAS
06/07/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 2ND FLOOR PLUMBING NOT PLUMBED PER PLAN OR CODE
2) NEED CLARIFICATION ON EXT. 1ST AND 2ND FLOOR ATTACHMENT, STRAPS AND BELLY BANDS
3) NAIL BOTTOM PLATE TO FLOOR 6" ON CENTER CAN ONLY, FIND DETAIL REFERING TO SHEARWALL, NOT REGULAR WALLS
4) FHA STRAP AT DRYER DUCT
5) TWO DAMAGED FLOOR TRUSSES, NEED REPAIR
6) OK TO INSULATE EXT. WALLS
7) REAR BATH TRAP ARMS TO LONG UNVENTED FIXTURES
8) 2" TRAP ARM OVER 5'-0", MUST GO 6" ABOVE FLOOD RIM BEFORE GOING HORIZONTAL
9) ITEM 03050 NOT REQUIRED/ALL ELECTRIC