Permit: T06CM02775

Parcel: 141095730

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM02775

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/18/2007 FRAMING Approved IVRS - Inspection :*
12/27/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INTERIOR BEARING WALL NOT CLIPPED BY GARAGE MAN DOOR
2) STAIR SHEARWALL REQUIRES CS20 STRAP ON END OF SHEAR
3) T8 HBC TRUSS NOT CLIPPED
4) INSTALL ROOF JACK ON PLUMBING
5) FILL HOLES IN ROOF
6) NAIL PROTECT PLUMBING
7) FIRE STOP B-VENT
8) FIRE STOP DUCT CHASE
9) STAIR LIGHT MUST BE 6'-8"
10) A/C COPPER OUT OF WALL
11) NAIL PROTECT REFRIDGERATOR PEX