Permit: T06CM02752

Parcel: 141095700


Addresses:

6351 E STAR MICA ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
01/17/2007 FRAMING Approved IVRS - Inspection :*
01/12/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 1,4,5,7,10 FOR 12/27/06 NOT DONE
12/27/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HOLDOWN WEST END OPF PATIO DOOR WEST PANEL NOT INSTALLED
2) CLIP INTERIOR BEARING WALL
3) NAIL PROTECT PLUMBING
4) STAIR HEADER MUST BEAR ON DBL 2 X ?
5) CS20 STRAP SHEARWALL
6) STAIR PONY WALL MUST BEAR 200 POUNDS SIDE LOAD
7) FIRE STOP W/H B-VENT
8) NAIL SECOND FLOOR SILL PLATES
9) A/C SECONDARY CONDENSATE MUST DRAIN IN A CONSPICOUS LOCATION OVER WINDOW OR DOOR
10) HOLDOWN BENT AND NUT LOOSE POWDER