Permit: T06CM02739

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM02739

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/04/2006 ELECTRIC - FINAL Approved
10/03/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PANEL DIRECTORY STILL NOT IDENTIFIED -- NEC 408.4
2. EMERGENCY LIGHTING STILL NOT PER CODE -- NEC 700.12(E)
3. ISOLATED GROUND TO CASH WRAP TO BE ISOLATED AND RAN WITH CKT CONDUCTORS -- NEC 250.134(B)
4. MAKE SURE ALL EQUIPMENT IS PROPERLY GROUNDED -- NEC 250.148

* WILL NEED TO PAY REINSPECTION FEE PRIOR TO FINAL APPROVAL.
10/02/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. EMERGENCY LIGHTING IS NOT PER PLAN & MISSING SOME LIGHTING.
2. EMERGENCY LIGHTING TO BE WIRED (POWERED BY) LIGHTING IN THE AREA IT SERVES -- NEC 700.12 (E)
3. PANEL DIRECTORIES ARE NOT PROPERLY IDENTIFIED --
NEC 408.4
4. IDENTIFY PANELS THEMSELVES IE. LP, MP
5. GROUND ALL METAL J-BOXES WITH EQUIPMENT GROUNDING CONDUCTOR AT CASH WRAP AND ANYWHERE ELSE BOXES ARE NOT GROUNDED -- NEC 250.148
6. STRAP ALL FLEX WITHIN 12" OF BOXES -- NEC 348.30
7. HAVE SOME DEAD RECEPTACLES, ALSO HAVE LOOSE RECEPTACLES/COVERS - TIGHTEN AS NEEDED - NEC 250.406.4
8. HAVE OPEN J-BOXES IN CEILING
9. INSTALL COVERS AND USE EXTENSIONS ON BATH GFI'S
09/29/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS -- ALSO, HAVE A COMPLETE SET OF PLANS ON SITE FOR ELECTRICAL FINAL.