Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM02739
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/04/2006 | ELECTRIC - FINAL | Approved | ||
10/03/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PANEL DIRECTORY STILL NOT IDENTIFIED -- NEC 408.4 2. EMERGENCY LIGHTING STILL NOT PER CODE -- NEC 700.12(E) 3. ISOLATED GROUND TO CASH WRAP TO BE ISOLATED AND RAN WITH CKT CONDUCTORS -- NEC 250.134(B) 4. MAKE SURE ALL EQUIPMENT IS PROPERLY GROUNDED -- NEC 250.148 * WILL NEED TO PAY REINSPECTION FEE PRIOR TO FINAL APPROVAL. |
|
10/02/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. EMERGENCY LIGHTING IS NOT PER PLAN & MISSING SOME LIGHTING. 2. EMERGENCY LIGHTING TO BE WIRED (POWERED BY) LIGHTING IN THE AREA IT SERVES -- NEC 700.12 (E) 3. PANEL DIRECTORIES ARE NOT PROPERLY IDENTIFIED -- NEC 408.4 4. IDENTIFY PANELS THEMSELVES IE. LP, MP 5. GROUND ALL METAL J-BOXES WITH EQUIPMENT GROUNDING CONDUCTOR AT CASH WRAP AND ANYWHERE ELSE BOXES ARE NOT GROUNDED -- NEC 250.148 6. STRAP ALL FLEX WITHIN 12" OF BOXES -- NEC 348.30 7. HAVE SOME DEAD RECEPTACLES, ALSO HAVE LOOSE RECEPTACLES/COVERS - TIGHTEN AS NEEDED - NEC 250.406.4 8. HAVE OPEN J-BOXES IN CEILING 9. INSTALL COVERS AND USE EXTENSIONS ON BATH GFI'S |
|
09/29/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS -- ALSO, HAVE A COMPLETE SET OF PLANS ON SITE FOR ELECTRICAL FINAL. |