Permit: T06CM02734


Addresses:

905 S CONCERT PL


Inspection Status: Partial Approval

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T06CM02734

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Partial Approval

Date Description Inspector Results Comments
05/24/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK TIE IN AT RAMADA
05/18/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G EXCEPT TIE IN OF LAST 10' AT RAMADA
OK 24" DEPTH
05/15/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PARTIAL U.G PVC SOUTH TO WEST & NORTH
POWER FEED NOT IN YET OR POLE BASES
PLANS CALL FOR 24" DEPTH - CONTR. INSTALLED U.G AT 18" BELOW GRADE PER PARK & REC'S REQUEST
APPROVAL BY INSPECTOR IS SUBJECT TO LETTER FROM ENGINEER OF RECORD APPROVING SUCH.