Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OS LIGHTS - 3 EXTERIOR INSTALLED 5 DELETED DELETION ON PLANS PER ELK'S REPRESENTATIVES WALT LEWANDOWSKI, TOM SHELBY |
|
| 12/18/2006 | ELECTRIC - FINAL | Denied | 1. PANEL DIRECTORYS STILL NOT CORRECT 2. ALARM PANEL STILL HAS NO EARTH GROUND. 3. DIMMER PACK AND MISSING COVER 4. INSTALL ALL DEVICE COVERS 5. OUTSIDE EMERGENCY LIGHTING NOT PROPERLY WIRED PROVIDE LADDER ACCESS TO ROOF. 6. EXTERIOR LIGHTING NOT PER PLAN. |
|
| 11/30/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. EMERGENCY LIGHTING TO BE FED FROM CKT IN THAT AREA NEC 700.12(E) 2. PANEL SCHEDULES TO BE CORRECTLY IDENTIFIED - NEC 408.4 AND NUMBER BREAKERS. 3. SECURE EMERGENCY LIGHTS TO STRUCTURE 4. FINISH BATHROOM AREAS 5. PROVIDE FOR DIMMER SYSTEM AS DISCUSSED 6. FINISH ALARM WIRING PROVIDE EARTH GROUND. 7. EXTERIOR LIGHTING NOT WORKING? |
|
| 11/29/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |