Permit: T06CM02732

Parcel: 115061660


Addresses:

1800 N ORACLE RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/22/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
OS LIGHTS - 3 EXTERIOR INSTALLED 5 DELETED
DELETION ON PLANS PER ELK'S REPRESENTATIVES
WALT LEWANDOWSKI, TOM SHELBY
12/18/2006 ELECTRIC - FINAL Denied 1. PANEL DIRECTORYS STILL NOT CORRECT
2. ALARM PANEL STILL HAS NO EARTH GROUND.
3. DIMMER PACK AND MISSING COVER
4. INSTALL ALL DEVICE COVERS
5. OUTSIDE EMERGENCY LIGHTING NOT PROPERLY WIRED
PROVIDE LADDER ACCESS TO ROOF.
6. EXTERIOR LIGHTING NOT PER PLAN.
11/30/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. EMERGENCY LIGHTING TO BE FED FROM CKT IN THAT AREA
NEC 700.12(E)
2. PANEL SCHEDULES TO BE CORRECTLY IDENTIFIED -
NEC 408.4 AND NUMBER BREAKERS.
3. SECURE EMERGENCY LIGHTS TO STRUCTURE
4. FINISH BATHROOM AREAS
5. PROVIDE FOR DIMMER SYSTEM AS DISCUSSED
6. FINISH ALARM WIRING PROVIDE EARTH GROUND.
7. EXTERIOR LIGHTING NOT WORKING?
11/29/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*