Permit: T06CM02732

Parcel: 115061660


Addresses:

1800 N ORACLE RD

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/22/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
11/14/2006 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) REMOVE BONDING CONNECTION BETWEEN BOND BUSHING AND NEUTRAL BLOCK IN SERVICE DISCONNECT-NEC 250.6 (LEAVE BUSHING BONDED FROM CT CAN)
10/18/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The service is not per code.| 210*
1. USE LISTED GUY SUPPORT FOR MAST -- NEC 230.28
2. SECURE FEEDER RACEWAY BETTER ON ROOF -- NEC 110.13
3. BONDING CONDUCTOR FOR MAST AND NIPPLE IS UNDERSIZED - NEC 250.102(C) AND MUST BE COPPER NOT ALUM NEC 250.102(A)
4. BOND ALL METAL PIPING TO SERVICE -- NEC 250.104
5. IDENTIFY SERVICE DISCONNECT -- NEC 230.70 B
6. GROUND FEEDER J-BOX WITH EQUIPMENT GROUND --
NEC 250.8
7. FEEDER EQUIPMENT GROUND TO BE #3 AL OR #2 CU --
NEC 250.122