Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 11/14/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) REMOVE BONDING CONNECTION BETWEEN BOND BUSHING AND NEUTRAL BLOCK IN SERVICE DISCONNECT-NEC 250.6 (LEAVE BUSHING BONDED FROM CT CAN) |
|
| 10/18/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. USE LISTED GUY SUPPORT FOR MAST -- NEC 230.28 2. SECURE FEEDER RACEWAY BETTER ON ROOF -- NEC 110.13 3. BONDING CONDUCTOR FOR MAST AND NIPPLE IS UNDERSIZED - NEC 250.102(C) AND MUST BE COPPER NOT ALUM NEC 250.102(A) 4. BOND ALL METAL PIPING TO SERVICE -- NEC 250.104 5. IDENTIFY SERVICE DISCONNECT -- NEC 230.70 B 6. GROUND FEEDER J-BOX WITH EQUIPMENT GROUND -- NEC 250.8 7. FEEDER EQUIPMENT GROUND TO BE #3 AL OR #2 CU -- NEC 250.122 |