Permit: T06CM02726

Parcel: 141331660


Addresses:

8335 S GUPTA DR


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T06CM02726

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
01/11/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
01/02/2007 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) ITEM #1 STILL NEED RETRO-WILL CHECK AT INTERMEDIATES
2) OK TO CONTINUE WITH BATH INSTALLATION OUTSIDE EXCEPT FOR THAT CORNER
12/06/2006 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) RETRO ON STHD 10 H.D. SOUTH EXT. WALL AT ENTRY
2) NEEDS STUDS WHERE THERE IS A BREAK AT BOTTOM PLATE-WILL INSPECT AT INTERMEDIATE
12/01/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TIGHTEN LOOSE ANCHOR BOLTS IN GARAGE WALLS
2) MISSING STHD10 HOLDOWN, SOUTH EXT. WALL
3) NAIL KING STUDS AT GARAGE WHERE THEY HAVE A H.D. ATTACHED TO IT
4) CUT HOLE IN PATIO COLUMN OSB, SO I CAN GET A VISUAL ON ANCHOR BOLTS
5) NEED PROTECTION STRAP NORTH EXT. WALL FOR CONDUIT AT KITCHEN