Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM02726
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/11/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
01/02/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) ITEM #1 STILL NEED RETRO-WILL CHECK AT INTERMEDIATES 2) OK TO CONTINUE WITH BATH INSTALLATION OUTSIDE EXCEPT FOR THAT CORNER |
|
12/06/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) RETRO ON STHD 10 H.D. SOUTH EXT. WALL AT ENTRY 2) NEEDS STUDS WHERE THERE IS A BREAK AT BOTTOM PLATE-WILL INSPECT AT INTERMEDIATE |
|
12/01/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TIGHTEN LOOSE ANCHOR BOLTS IN GARAGE WALLS 2) MISSING STHD10 HOLDOWN, SOUTH EXT. WALL 3) NAIL KING STUDS AT GARAGE WHERE THEY HAVE A H.D. ATTACHED TO IT 4) CUT HOLE IN PATIO COLUMN OSB, SO I CAN GET A VISUAL ON ANCHOR BOLTS 5) NEED PROTECTION STRAP NORTH EXT. WALL FOR CONDUIT AT KITCHEN |