Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM02720
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/19/2006 | FRAMING | Approved | IVRS - Inspection :* | |
12/14/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHIM ALL LET INS AT EXTERIOR WALLS 2) NEED BLOCKS ON COMBUSTION AIR VENT DUCT-GARAGE 3) NEED CAULK ALL CUT OUT 4) BACK ROOF VENT NOT COMPLETED 5) SEAL HOLES IN VAPOR RETARDER 6) MISSING ANTI SIPHON ON HOSE BIBS 7) NO DWV TEST 8) PRESSURE GAUGE READING ZERO |
|
11/30/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIRE STOP AT POP OUT 2) SHIM HEADERS 3) NEED TO SEAL ALL CUT OUTS FOR RECEPTACLES 4) BAY WINDOW NOT COMPLETED 5) NEED TO SHORTEN PRESSURE RELIEF OF DRAIN OUTSIDE OF BLDG 6) NO PRESSURE ON GAS GAUGE 7) MOVE GAS LINE 12" FROM CAN LIGHT IN KITCHEN 8) NO DWV TEST 9) NO PRESSURE TEST 10) A/C LINE INSULATION TURN AT CLOSET |