Permit: T06CM02712

Parcel: 136313180

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
03/31/2008 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
01/25/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G FOR POLE LIGHTS
01/23/2008 ELECTRIC - UNDERGROUND Partial Approval OK 3 REMAINING POLE BASES
01/11/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK UG @ DISPENSING UNITS
2. OK UG TO UNDERGROUND TANKS
12/27/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK CONTINUATION OF 1" PVC 60' HEADING OUT TO PUMPS
12/19/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 6 POLE BASES NORTH SIDE OF PROPERTY AND
AT DUMPSTER LOCATION
11/02/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 4 - 4" PVC FROM TEP XFMR TO SES
2. INSTALL WARNING RIBBONS ABOVE SERVICE ENTRANCE CONDUCTORS PER NEC 300.5
09/07/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK RIGID & PVC CONDUITS FROM STORE
HEADING OUT TO GAS PUMPS 20'
09/04/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK (5) 2 1/2" PVC IN BUILDING SLAB FOR PANEL FEEDERS.
2. OK 3/4" PVC IN BUILDING SLAB FOR BRANCH CIRCUITS.
3. OK 2" PVC FOR TELEPHONE