Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
| 06/26/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PANEL "A" NOT REFLECTIVE OF WORK INSTALLED 2. LABEL CIRCUITS AS PER 408.4 -- NO ABBREVIATIONS ROOF: 1. SUPPORT JUNCTION BOXES WITH OTHER THAN CONDUIT 2. TIGHTEN LOOSE FITTINGS 3. WHERE ARE MAINTENANCE RECEPTACLES PER 210.63 |
|
| 03/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* |
|
| 10/03/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MAINTAIN WORKING CLEARANCE IN FRONT OF PANELS. 2. SECURELY MOUNT BOX TO STRUCTURE. 3. CORDS NOT ALLOWED ABOVE CEILING 4. SHEETMETAL SCREWS NOT ALLOWED FOR GROUNDING. 5. PANEL CIRCUITS & LOADS DO NOT MATCH PLANS. REVISE PLANS WITH CIRCUITING & LOADS. PLANS TO HAVE NEW STAMP. * CHECK ROOF NEXT INSPECTION. |
|
| 08/07/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FINISH PREVIOUS ITEMS |
|
| 08/05/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |