Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/06/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/01/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* |
|
| 08/18/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/09/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | OK WALK INS & OK COFFEE BAR AREAS TO USE (ELEC. ONLY) | |
| 08/08/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/07/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 08/05/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SECURE BOXES UNDER COFFEE BAR 2. TIGHTEN LOOSE FITTINGS 3. GROUND JUNCTION BOXES ABOVE WALK IN/COOLER BOXES ON ROOF, AT DISCONNECT ENCLOSURE. 4. LABEL ROOF DISCONNECTS 5. NO MORE THAN 360 DEG. IN A CONDUIT RUN-ROOF & SUPPORT CONDUIT. 6. DRAIN TO BE RE-ROUTED FROM DRIPPING ON SERVICE. JASON JAWORSKY 909-5147 TO SCHEDULE APPT. OK SODA & FAST FOOD AREA ELECTRIC AT COUNTER FINISH ROOF RECEIVED LETTER FOR DIECAST FITTINGS. |
|
| 08/03/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. VERIFY BOX FILL 2. CHASE NIPPLES NOT APPROVED FITTINGS FOR OTHER THAN PASS THRU. 3. PROTECT & SUPPORT M/C CABLE 4. M/C CABLE NOT TO BE MODIFIED 5. NO MORE THAN 360 DEG. IN A CONDUIT RUN 6. FINISH SECURING PANEL "B" & CORRECT PHASE COLORING 7. PLEASE PROVIDE A LETTER FOR USAGE OF DIE CAST FITTINGS 8. FINISH PREVIOUS ITEM #1 |
|
| 07/07/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NEED REJECTION PINS |
|
| 07/06/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* MEET WITH CONTRACTOR TO DISCUSS JOB PROGRESS |