Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 07/26/2006 | MECHANICAL - FINAL | Partial Approval | OK PER STEVE LONG PER INSPECTOR | |
| 07/21/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE ALARMS & RESET FOR DUCT SMOKE DETECTOR. |
|
| 07/19/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE AN AUDIBLE & VISIBLE ALARM FOR DUCT SMOKE DETECTOR AS PER 2003 IMC PAINT EXPOSED PVC W/LATEX PAINT. |
|
| 07/16/2006 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/14/2006 | MECHANICAL - FINAL | Not ready for Inspection | ||
| 07/13/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 07/12/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 07/10/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 3/8" I.D GAS FLEX NOT ADEQUATE FOR 125,000 BTU WATER HEATER. PROVIDE FLUE VENTING. STRAP UP FLEX DUCTS. USE A METAL CONNECTOR WHEN SPLICING FLEX DUCT. FINISH ALL WORK ON ROOF SCHEDULE AN ABOVE CEILING INSPECTION. WHERE IS THE DUCT SMOKE DETECTOR AS PER PLANS? |