Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06CM02695
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/21/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
07/19/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SEE ITEM #2 FROM 7/12/06 2. WATER HEATER VENTING TO BE PER INSTALLATION INSTRUCTION CORRECTIONS ABOVE FOR FINAL. RECEIVED LETTER FROM ENGINEER GIVING OK FOR (2) FLOOR DRAINS IN PLACE OF FLOOR SINKS IN TUB ROOM. |
|
07/17/2006 | PLUMBING - FINAL | Cancelled | CANCELLED PER CONTRACTOR DAN #925-917-0243 | |
07/17/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
07/14/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLUMBER TO COMPLETE ITEMS FROM 7/12/06 THIS SECTION OF BUILDING IS OCCUPIED WITHOUT FINAL INSPECTION. RED TAG HAS BEEN ISSUED AND RICK SANCHEZ MANAGER FROM THIS PETCO WAS INFORMED TO VACATE THIS AREA OF BUILDING WITH PETS & EMPLOYERS. DON YOUNG, HARDESTY & ASSOC. HAS ALSO BEEN INFORMED. |
|
07/12/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE LETTER PER REQUEST ON NOTE FROM 03075 INSPECTION 6/6/06 2. PROVIDE CORRECT BACKFLOW PROTECTION FOR HAND SPRAYER FOR TUBS. 3. PROVIDE INSTALL INSTRUCTIONS FOR WATER HEATER & VIEWING OF VENT CONNECTIONS TO HEATER. 4. COMPLETE ALL PLUMBING WORK NOT A COMPLETE LIST. |