Permit: T06CM02695

Parcel: 12708187F


Addresses:

5405 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM02695

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/19/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/17/2006 ELECTRIC - FINAL Cancelled CANCELLED PER CONTRACTOR DAN #925-917-0243
07/17/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/14/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/12/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. FINISH WALL IN TUB ROOM NOTE 314.20
2. FINISH PREVIOUS ITEMS.
07/12/2006 ELECTRIC - FINAL Not ready for Inspection RECEIVED MONEY ORDER #08-499627548 FOR $108.00
UNSCHEDULED INSPECTION.
1. MAINTAIN WORKING CLEARANCE IN FRONT OF TRANSFORMER 110.26
2. ENTRANCES NOT TO BE ABOVE COILS AS PER INSTRUCTIONS
3. ENCIRCLE GROUND CONDUCTORS WITH MARKING TAPE 250.119
4. BLACK OR GREEN TAPE IS NOT AN APPROVED SUPPORTING METHOD.
5. PLEASE PROVIDE A LETTER FOR LIGHTING CONNECTED TO EXISTING CIRCUIT.
6. SUPPORT CONDUIT WITHIN 3' OF ABOVE SERVICE
7. SUPPORT SPEAKER & WIRE ABOVE GRID OR REMOVE.
07/10/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. USE A TERMINAL END FOR STRANDED CONDUCTORS.
2. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN PANEL & TRANSFORMER FOR INSPECTION.
3. WHERE IS LIGHTING CIRCUIT AS PER PLANS?
4. ONLY ONE CONDUCTOR PER TERMINAL SCREW (W/H)