Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM02695
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/19/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/17/2006 | ELECTRIC - FINAL | Cancelled | CANCELLED PER CONTRACTOR DAN #925-917-0243 | |
07/17/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
07/14/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
07/12/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FINISH WALL IN TUB ROOM NOTE 314.20 2. FINISH PREVIOUS ITEMS. |
|
07/12/2006 | ELECTRIC - FINAL | Not ready for Inspection | RECEIVED MONEY ORDER #08-499627548 FOR $108.00 UNSCHEDULED INSPECTION. 1. MAINTAIN WORKING CLEARANCE IN FRONT OF TRANSFORMER 110.26 2. ENTRANCES NOT TO BE ABOVE COILS AS PER INSTRUCTIONS 3. ENCIRCLE GROUND CONDUCTORS WITH MARKING TAPE 250.119 4. BLACK OR GREEN TAPE IS NOT AN APPROVED SUPPORTING METHOD. 5. PLEASE PROVIDE A LETTER FOR LIGHTING CONNECTED TO EXISTING CIRCUIT. 6. SUPPORT CONDUIT WITHIN 3' OF ABOVE SERVICE 7. SUPPORT SPEAKER & WIRE ABOVE GRID OR REMOVE. |
|
07/10/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. USE A TERMINAL END FOR STRANDED CONDUCTORS. 2. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN PANEL & TRANSFORMER FOR INSPECTION. 3. WHERE IS LIGHTING CIRCUIT AS PER PLANS? 4. ONLY ONE CONDUCTOR PER TERMINAL SCREW (W/H) |