Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM02669
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/25/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/20/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO INSTALL CEILING TILES MATT COMMONWEALTH ELEC. |
|
10/17/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* CORRECTIONS FROM PREVIOUS INSPECTION NOT COMPLETE ALSO, CHECK J-BOX FILL AND GROUNDING AND REMOVE OR TAG ALL LOW VOLTAGE WIRING THAT IS ABANDONED. BOX FILL CHART NEC 314.16A CHARLIE 349-5029 |
|
10/13/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SECURE FIXTURES TO GRID -- NEC 300.11 2. SUPPORT WIRES TO BE SECURED @ BOTH ENDS -- NEC 300.11 3. PROVIDE SUPPORT WIRES FOR TRACK LIGHTING -- NEC 410.104 4. MC WIRING TO BE SECURED WITHIN 12" OF TERMINATIONS AND 6' INTERVALS. NEC 330.30 5. FINISH PULLING BRANCH CKT'S AND PROVIDE TALL LADDER SO I CAN CHECK J-BOXES. FINISH ALL WIRING IN CEILING AND DO NOT CALL UNTIL READY ALL LIGHTING FIXTURES AND RACEWAYS/EQUIPMENT TO HAVE SUPPORT WIRES INDIVIDUAL OF GRID SUPPORT WIRES. |