Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
10/25/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
10/20/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO INSTALL CEILING TILES
MATT COMMONWEALTH ELEC.
10/17/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
CORRECTIONS FROM PREVIOUS INSPECTION NOT COMPLETE
ALSO, CHECK J-BOX FILL AND GROUNDING AND REMOVE OR TAG ALL LOW VOLTAGE WIRING THAT IS ABANDONED.

BOX FILL CHART
NEC 314.16A

CHARLIE 349-5029
10/13/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SECURE FIXTURES TO GRID -- NEC 300.11
2. SUPPORT WIRES TO BE SECURED @ BOTH ENDS --
NEC 300.11
3. PROVIDE SUPPORT WIRES FOR TRACK LIGHTING --
NEC 410.104
4. MC WIRING TO BE SECURED WITHIN 12" OF TERMINATIONS AND 6' INTERVALS. NEC 330.30
5. FINISH PULLING BRANCH CKT'S AND PROVIDE TALL LADDER SO I CAN CHECK J-BOXES.

FINISH ALL WIRING IN CEILING AND DO NOT CALL UNTIL READY ALL LIGHTING FIXTURES AND RACEWAYS/EQUIPMENT TO HAVE SUPPORT WIRES INDIVIDUAL OF GRID SUPPORT WIRES.