Permit: T06CM02660


Addresses:

8467 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/13/2006 ELECTRIC - FINAL Approved PER LINDA B.
07/12/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
07/05/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FILL UNUSED OPENINGS IN "MCCA"
2. LABEL "MCCA" AND OUTSIDE DISCONNECTS.
3. MISSING GUTTER COVER OUTSIDE
4. FUSING NOT AS PER PLANS.
5. VDV CABELING MISSING COVER PLATES AND TIGHTEN LOOSE FITTINGS.
06/28/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) NEED TO TEST DUCT SMOKE DETECTORS
2) CUT THREADS OFF PRESSURE RELIEF DRAIN
3) SUPPORT SENSING TUBS FROM SMOKE DETECTORS
06/26/2006 ELECTRIC - FINAL Cancelled IVRS - RI canceled