Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - SECURE LOW VOLTAGE CONDUIT ON ROOF. - CONDENSATE CANNOT TERMINATE INTO A SEWER VENT TERMINATE TO WITHIN 6" OF THE GROUND. - DO NOT DRAIN ONTO A HARD SURFACE. - PAINT EXPOSED PVC W/LATEX PAINT. BLOCK & CLAMP EVERY 4" - MARK THE UNIT DATA PLATE W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY ON CIRCUIT BREAKER. - SUPPORT DUCT AT CANVAS CONNECTORS. - IDENTIFY CIRCUIT BREAKER. |