Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM02618
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/09/2007 | ELECTRIC - ABOVE CEILING | Approved | ||
12/13/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* LOW VOLTAGE WIRING TO BE COMPLETED OK TO INSTALL CEILING TILES, WILL CHECK CEILING AGAIN ON FINAL |
|
12/12/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ALL FIXTURES NEED SUPPORT WIRES. 2. SUPPORT WIRES FOR EQUIPMENT TO BE SECURED @ BOTH ENDS - NEC 300.11 3. FILL UNUSED OPENINGS - NEC 110.12A 4. SECURE MC WITHIN 12" OF TERMINATIONS - NEC 330.30 5. USE PROPER SIZE STRAPS FOR RACEWAYS -- NEC 110.3 6. STILL HAVE OVERFILLED BOXES -- NEC 314.16 AND MAKE SURE ALL ARE GROUNDED. 7. FINISH ALL WIRING IN CEILING. WILL HAVE FEE IF NOT CORRECT NEXT INSPECTION. |
|
12/08/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED SUPPORT WIRES FOR ALL FIXTURES, SECURE FIXTURES TO GRID, FILL UNUSED OPENINGS -- TRACK INCLUDED. 2. HAVE OVERFILLED J-BOXES AND MAKE SURE ALL ARE GROUNDED. 3. MC TO BE STRAPPED WITHIN 12" OF TERMINATIONS AND SUPPORTED AT PROPER INTERVALS -- NEC 330 WORK ABOVE CEILING NOT COMPLETE CALL WHEN COMPLETE AND REMOVE CEILING TILES. GRID SUPPORT WIRES NOT TO SUPPORT OTHER EQUIPMENT NEC 300 |
|
10/27/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |