Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/27/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/26/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PROPERLY GROUND POLE LIGHTS 2. RECALL WHEN READY |
|
| 04/19/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. LABEL CIRCUIT DIRECTORY AS PER 408.4 - NO ABBREVIATIONS 2. INSTALL ALL STRANDS UNDER TERMINAL -- CONTACTORS 3. VERIFY DERATING PER 310.15 4. SUPPORT VDV CABELING 725.6 5. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLES FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING 314.20 6. TIGHTEN ALL LOOSE SEAL TITE FITTINGS 7. WHERE IS PHOTO CELL AS PER PLANS 8. CHECK OWNERS PANEL NEXT TIME AND POLE LIGHTING |