Permit: T06CM02615

Parcel: 13325186E


Addresses:

8474 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
10/18/2006 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
09/28/2006 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
MEET WITH PAT THE DEVELOPER, DAVE FROM
BARKER MORRISSEY, PAUL FROM ARCOSTAR ELECTRIC, AND JASON & RICK OF DSD.
WE DISCUSSED OBJECTIVENESS OF JOB. PAT WILL PROVIDE SOIL ENGINEER'S REPORT TO DETERMINE DEPTHS. PAUL WILL PROVIDE REPORT FROM TEP. DIGGING WILL OCCUR AT SINGLE PHASE SERVICE AND END OF CONDUIT RUN NORTH POLE BASE. MANDRILL PULLS WILL BE IN ALL 3 PHASE PRIMARY CONDUITS. (6) PAUL WILL CALL FOR INSPECTION TO WITNESS MANDRILL PULLS. CORRECTION ITEMS AT SERVICE WILL BE COMPLETED FOR INSPECTION.
09/27/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
MEET WITH DAVE FROM BARKER MORRISSEY TO DISCUSS WHERE TO DIG OPEN DIRT AREAS AS DISCUSSED AT THIS TIME. ALSO A MANDRAIL PULL FOR ALL CONDUITS WILL NEED TO BE PERFORMED. INSPECTOR WILL NEED TO WITNESS AS PER JASON JAWORSKY.
09/26/2006 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
1. WHITE CONDUCTOR NOT TO BE TAPE MARKED A PHASE CONDUCTOR PULL THHN A COLOR THROUGH RACEWAY.
2. PLEASE HAVE SOMEONE MEET ME ON SITE TO DISCUSS POTHOLES AND OPENING OF DIRT TRENCHES.