Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* - FLANGES OK - OPEN DRAINS SHOULD REMAIN PLUGGED UNTIL FIXTURES ARE SET AND TRAPS FILLED W/WATER. - LAV CARRIERS? |
|
| 12/13/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WALLS AND ABOVE CEILING ARE OK TO COVER |
|
| 12/06/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. TESTS OK 2. SECURE ABS IN WALL 3. INSTALL SAFETY PLAES 4. INSULATE HW 5. SUPPORT 1" AT 6' 6. SECURE CLOSET FLANGES - READ UPC INSTALLATION STANDARDS #5 UNDER "SUPPORT" FOR PROPER FLANGE INSTALLATION. 7. DON'T FORGET TAPPED CO PLUGS AND LAVITORY TEMP LIMITING DEVICES FOR FINAL. |