Inspection History Details
Permit: T06CM02601
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/10/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TO ENERGIZE WELLS FOR TESTING 2) 1 WIRE TERMINATION AT GROUND ROD LUGS. INSTALL 2ND GROUND LUG AT GROUND RODS 3) CANNOT TERMINATE 2 WIRES UNDER LUG IN DISCONNECT. INSTALL DBL LUG OR 2ND SINGLE LUG 4) PREVIOUS INSPECTION ITEMS CORRECTED |
|
| 08/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CONNECT GROUNDING ELECTRODE CONDUCTOR TO DISCONNECT SERVING EACH WELL SITE -- NEC 250.32 2. GROUNDING CONDUCTORS SMALLER THAN #6 NEED TO BE INSTALLED IN RACEWAY NEC 250.64 3. COMPLETE ALL ITEMS FROM PREVIOUS INSPECTIONS 4. RECEIVED DEPTH REPORTS ON UNDERGROUND. 5. UNDERGROUND OK |
|
| 08/06/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY MIKE @ MOUNTAIN POWER |
|
| 06/22/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CONDUCTORS OTHER THAN SERVICE CONDUCTORS SHALL NOT BE INSTALLED IN THE SAME RACEWAY -- NEC 230.7 2. NEED TO INSTALL NEUTRAL/GROUND KIT AT NEW SERVICE DISCONNECT FOR IT TO BE RATED AS SERVICE EQUIPMENT NEC 110.3 & 230.70 3. MARK "SERVICE DISCONNECTS" NEC 230.70 4. NEED TO INSTALL NEUTRAL CONDUCTOR TO SERVICE DISCONNECTS -- NEC 250.24 5. GEC TO BE CONNECTED TO NEUTRAL - NEC 250.24 6. PVC RUN TO NEW WELL PUMPS NEVER INSPECTED FOR UNDERGROUND ELECTRICAL FOR AFTER HOURS INSPECTION CALL JASON JAWORSKY 909-5147 |