Permit: T06CM02601

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/14/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/10/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK ON DEPTH, LISTING & CONNECTIONS OF UNCOVERED UNDERGROUND PVC INSTALLATION. FINAL APPROVAL ON UNDERGROUND PENDING ELEVATION REPORTS TO BE SUBMITTED BY CONTRACTOR.
2. SIGNING CIRCUITS CANNOT BE INSTALLED IN SAME HANDHOLE ENCLOSURE WITH POWER CONDUCTORS --
NEC 725.55
3. PLEASE PROVIDE INFORMATION THAT ALLOWS INSTALLATION OF FIBER OPTIC CABLES IN SAME HANDHOLE ENCLOSURE WITH POWER CONDUCTORS.
07/06/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
FIELD MEETING TO RESOLVE ISSUES. CONTRACTOR TO PROCEED WITH CORRECTIONS DISCUSSED AT MEETING.
RAY MAJUTA AND JASON JAWORSKY ATTENDEES.
06/29/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
THERE ARE SEVERAL CONCERNS WITH THIS PROJECT
1. THE DISCONNECTS & TRANSFORMER ARE BEING INSTALLED UNDERGROUND IN OPEN BOTTOM VAULTS. IT APPEARS TO ME UNDER HEAVY RAIN OR FLOODING THE VAULT COULD FILL UP WITH WATER & ENTER ALL THE EQUIPMENT.
2. THOUSANDS OF FEET OF PVC HAS BEEN INSTALLED UNDERGROUND WITH NO INSPECTIONS.
3. UNDERGROUND SPLICES IN HARD HOLE ENCLOSURES NEED TO BE LISTED FOR WET LOCATION
4. WORKING CLEARANCES IN FRONT OF DISCONNECTS & TRANSFORMERS IN VAULT WILL NOT BE MEET PER NEC 110.26
5. THE METAL WELL CASING AT EACH WELL SITE SHOULD
BE USED AS PART OF GROUNDING ELECTRODE SYSTEM
PER NEC 250.30 & 250.52
6. THE MAIN DISCONNECT AT EACH SITE SHOULD BE CONNECTED WITH GROUNDING ELECTRODE CONDUCTOR TO GROUNDING ELECTRODES PER NEC 250.32
7. NO FINAL WILL BE GIVEN UNTIL THESE ISSUES HAVE BEEN RESOLVED.
06/25/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
06/25/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK SERVICE INSPECTION
2. MARK "SERVICE DISCONNECTS" PER NEC 230.70

CALLED TEP MAP ROOM FOR CLEARANCE PERMIT WAS PULLED UNDER THIS ADDRESS ACTUAL ADDRESS OF METER IS
7323 S SWAN RD

RECEIVED CHECK FROM RICKY GLASSER FOR $108.00
FOR AFTER HRS. INSPECTION CHECK #199
06/22/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*