Permit: T06CM02596

Parcel: 141014530

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM02596

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/07/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/19/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SECURE ALL E.M.T WITHIN 3' OF J-BOXES
2. TIGHTEN ALL EQUIP. GROUNDING CONNECTION & ONE HAS FALLEN OUT (GROUNDING SCREW) COMPLETELY.
3. SET SCREW FITTING ARE NOT CONSIDERED OK FOR OUTDOOR USE WHERE SUBJECT.
4. PLANS CALL FOR 30 AMP. 2 POLE BREAKER NOT 15 AMP.